Voltage drop calculator
Pick the system, voltage, conductor and wire size, then enter the load and the length. Get the drop in volts and percent.
- Voltage drop
- 5.27%
- Volts lost
- 6.32 V
- Voltage at the load
- 113.7 V
- Smallest size for 3% or less
- 8 AWG
The formula
Single phase: voltage drop = 2 × K × current × length ÷ circular mils. Three phase uses 1.732 (the square root of 3) in place of 2. K is the resistance constant, 12.9 for copper and 21.2 for aluminum, and the circular mils for each size come from NEC Chapter 9, Table 8.
This is the standard estimate. It doesn't account for power factor, reactance on large conductors, or conductor temperature, which matter more on long, heavily loaded runs.
Electricians can't answer the phone with their hands in a panel. See how an electrician answering service gets the job details and books the visit while you work.
Questions
How much voltage drop is acceptable?
The NEC's informational notes suggest no more than 3% on a branch circuit and 5% in total for the feeder and branch circuit together. They're recommendations, not requirements, but most electricians design to them.
Does this tell me the right wire size?
Only for voltage drop. A wire also has to carry the current safely, so check its ampacity, the temperature rating of the terminals, and your local code before you choose a size.
What length should I enter?
The one-way length from the panel or source to the load, in feet. The formula already accounts for the current going out and back.
More free tools
- Roofing calculatorRoof area, squares and shingle bundles from the footprint and pitch.
- Roof pitch calculatorPitch, angle and area multiplier from rise and run.
- BTU and AC tonnage calculatorHow much cooling a room or small home needs, in BTU and tons.
- Invoice and estimate makerMake a printable invoice or estimate for a job in a minute.
Stop missing calls for good
CallFrontDesk answers every call, books the job and emails you the details. Set it up in an afternoon.